HVAC Maintenance in san antonio
Ambient Tech Solutions llc will check in and out daily with contact on site. All Equipment serviced will be recorded in maintenance log sheets and sent to client with invoice or a reference number with the invoice. All debris, waste, and discarded materials generated during the service will be collected and disposed of in the client's designated on-site dumpster or waste disposal area in a clean and professional manner, ensuring the worksite is left in a tidy condition. We offer 1 time visits, or Maintenance Contracts with scheduled service visits.Maintenance Contract includes discount benefits,no diagnostic fees, and no emergency rate fees. Maintenance services are fully customizable with even the option of client providing filters. Call for a Free Estimate.
RUN INSPECTION
-
Change all customer provided filters (filters are to be dated as being installed) and clean or replace pre-filters/air cleaners, Clean filter medias
-
Inspect all belts and pulleys for alignment, tension and wear.
-
Inspect for visible Leaks Water/Refrigerant
-
Inspect all contactors and internal electrical wiring checked for loose connections and/or burnt wiring.
-
Inspect Condition of Evaporator and Condenser Coil
-
Check operation and conditions of exhaust fans; Inspect Belts.
-
Inspect Mechanical Integrity of all moving parts.
-
Check Delta-T on supply and return.
-
Check all internal controls and safety devices within equipment.
-
Inspect Condensate Drain Pan and Drain Lines.
-
Inspect Water hoses, water valves,
-
Log equipment performance and report all deficiencies to client in a timely manner.
-
Check all motor amp draws to name plate design.
-
Check Voltage to name plate design.
-
Check Psi, subcooling, superheat if a failure is detected via Delta-T or Fla.
-
On ice machine's; inspect water filter, inspect bin, inspect bin switch/ice level sensor, inspect evaporator plate for scale. Test auger where applicable.
PREPARATION FOR SUMMER
Unless prohibited by continued cold weather, all HVAC must be checked, cleaned and ready for service before cooling season. Peak efficiency is a must. All HVAC equipment is to be cleaned, in good working condition and ready for reliable service for the cooling season. Inspections to include.
-
Change all customer provided filters (filters are to be dated as being installed) and clean or replace pre-filters/air cleaners, check condenser hose kit strainers. Clean filter medias
-
Inspect all belts and pulleys for alignment, tension and wear.
-
Inspect Condition of Evaporator and Condenser Coil
-
Replace belt as required (once per Calander year).
-
Lubricate all equipment per manufacturer's specs.
-
Inspect all contactors and internal electrical wiring checked for loose connections and/or burnt Wiring.
-
Inspect Mechanical Integrity of all moving parts.
-
Check all motor amp draws to name plate design.
-
Check Voltage to name plate design.
-
Non-Chemically Clean outdoor condenser coils.
-
Check Delta-T on supply and return.
-
Inspect for visible Leaks Water/Refrigerant
-
Inspect Water hoses, water valves,
-
Check all refrigerant pressures for correct charge on non-critical charged systems.
-
Check operation and conditions of exhaust fans; Inspect Belts.
-
On rooftop exhaust fans; inspect grease catcher and clear if needed
-
Check all internal controls and safety devices within equipment.
-
Clear Drain lines
-
Vacuum and clean drain pans & piping as needed.
-
Check all motor amp draws to name plate design.
-
Check supply and return air flow, verify functionality of mechanical venting systems.
-
Log equipment performance and report all deficiencies to client in a timely manner.
-
On ice machines; Clean and sanitize ice machine and ice machine Bin
-
On ice machine's; inspect water filter, inspect bin, inspect bin switch/ice level sensor, inspect evaporator plate for scale. Test auger where applicable.
-
Drain water tank where applicable
​
​
PREPARATION FOR WINTER
​
This check is intended to winterize the building. The heating equipment must be cycled and the entire heating system thoroughly inspected to confirm that the system will function in a safe, dependable manner. Inspections to include, but not limited to, items listed below.
-
Change all customer provided filters (filters are to be dated as installed) and clean or replace pre-filters/air cleaners. Clean filter medias
-
Check operation and conditions of exhaust fans; Inspect Belts.
-
On rooftop exhaust fans; inspect grease catcher and clear if needed
-
On Heat pumps in heat mode; check psi, subcooling, superheat
-
Clear Drain Lines
-
On ice machines; Clean and sanitize ice machine and ice machine Bin
-
On ice machine's; inspect water filter, inspect bin, inspect bin switch/ice level sensor, inspect evaporator plate for scale. Test auger where applicable.
-
Test all heaters gas, electric, heat pumps.
-
Inspect all belts and pulleys for alignment, tension and wear.
-
Replace belt as required (only once per Calander year).
-
Lubricate all equipment per manufacturer's specs.
-
Check all motor amp draws to name plate design.
-
Check Voltage to name plate design.
-
Check electric and gas ignition systems, tune as needed.
-
Check heat exchanger integrity.
-
Amp draws on all electric heaters.
-
Verify combustion air dampers, motors and louvers are free and functional
-
Check water psi and temperatures where applicable
-
Check all safety devices, controls, and relief valves for correct operation and function.
-
Verify safe C02 levels on combustion heaters.
-
Check heat tracing on piping. (Where applicable)
-
Check defrost control for operation.
-
Shut down any dangerous equipment and report.
-
Check sump heaters and make up water for leaks. (if applicable)
-
Secure doors to prevent loss, including exhaust fan caps/Lids.
-
Log equipment performance and report all deficiencies to client in a timely manner.
-
Clean burner area once per year
-
Inspect for visible Leaks Water/Refrigerant
-
Inspect Water hoses, water valves,
-
Drain water tank if applicable